Key points
- kVA is apparent power. For three phases, kVA = √3 × voltage × current ÷ 1,000: a 1,000 kVA transformer at 400 V carries about 1,443 A.
- IEC 60076-1 prefers ratings from the R10 series (100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1,000 kVA and on), but each utility keeps its own list.
- Oil-immersed units suit outdoor substations, cast-resin dry-type units suit indoor rooms, and CSP and pad-mounted units serve utility networks.
- ONAN means oil, natural oil flow, air, natural air flow; ONAF adds fans. Dyn11 is a common distribution connection, and PEA specifies it.
- Losses are limited by regulation, the utility or the tender: EU Tier 2 since July 2021, PEA and Saudi Energy (formerly Saudi Electricity Company) specifications, and Thailand’s voluntary No. 5 label.
Simplified drawing, not to scale.
- Pole-mounted (CSP) transformer on an overhead medium-voltage line, with a low-voltage line to houses
- Pad-mounted transformer on the ground, fed by an underground cable
- Cast-resin transformer in an indoor electrical room of a building
- Oil-immersed transformer outdoors beside a factory
- Power transformer in a utility substation, fed from a high-voltage line
- Medium-voltage network: overhead lines and underground cables
What a distribution transformer does
A transformer changes the voltage and keeps the frequency. A distribution transformer takes the medium voltage of the utility network — in Thailand 22 or 33 kV with PEA, 12 or 24 kV with MEA — and steps it down to the low voltage that buildings and machines use, such as 400/230 V. Siemens Energy describes its liquid-immersed distribution transformers as typically up to 36 kV on the primary side and 250–800 V on the secondary side.
The EU ecodesign regulation calls a transformer with a highest voltage for equipment above 1.1 kV and up to 36 kV, rated from 5 kVA to below 40 MVA, a medium power transformer, and sets maximum losses for it.
Schematic, not to scale.
- Core: carries the magnetic field that links the windings
- Low-voltage winding, next to the core
- High-voltage winding, around the low-voltage winding
- Insulating liquid (mineral oil or an ester): insulates the windings and carries their heat to the tank
- Corrugated wall: in a hermetically sealed tank it flexes as the oil expands and contracts (Siemens Energy)
- High-voltage bushing
- Low-voltage bushing
- Off-circuit tap changer handle, turned only with the transformer switched off
- High-voltage coil cast in epoxy resin, cooled by air
- Tapping links, changed only with the transformer switched off
- Low-voltage terminals
- Fans for forced-air cooling (AF), where fitted
What kVA means
A transformer is rated by its rated power in kVA: the apparent power that, with the rated voltage, sets the rated current (IEC 60076-1). Apparent power counts the whole current, whatever the power factor of the load, so the rating is given in kVA rather than kW.
- Real power (kW): what the loads turn into work and heat
- Reactive power (kVAr), drawn by motors and other inductive loads
- Apparent power (kVA): what the transformer must carry
- Power factor = kW ÷ kVA, the cosine of this angle
- Voltage between two lines (U), for example 400 V
- Current in each line (I)
- Three-phase: kVA = √3 × U (V) × I (A) ÷ 1,000. The other way round, full-load current I = kVA × 1,000 ÷ (√3 × U).
- From kW: kVA = kW ÷ power factor. A load of 800 kW at a power factor of 0.85 needs about 941 kVA before any spare capacity.
- On the rating plate: IEC 60076-1 requires the rated power, frequency, rated voltages and tapping range, rated currents, vector group, short-circuit impedance and type of cooling, among others.
- Rated voltage is a no-load value (IEC 60076-1). That is why a transformer for a 400/230 V network can show 416/240 V on its plate, as in PEA’s specification for its own distribution transformers.
| Rating | Full-load current at 400 V |
|---|---|
| 100 kVA | 144 A |
| 160 kVA | 231 A |
| 250 kVA | 361 A |
| 400 kVA | 577 A |
| 630 kVA | 909 A |
| 800 kVA | 1,155 A |
| 1,000 kVA | 1,443 A |
| 1,250 kVA | 1,804 A |
| 1,600 kVA | 2,309 A |
| 2,000 kVA | 2,887 A |
| 2,500 kVA | 3,608 A |
To size a transformer from the connected load, demand factor and power factor, use the transformer kVA calculator.
Standard kVA ratings
There is no single list. IEC 60076-1 recommends that ratings up to 20 MVA be taken from the R10 series of preferred numbers — 100, 125, 160, 200, 250, 315, 400, 500, 630, 800 and 1,000 kVA, and on through the same series — and notes that national practices may differ. Regulators, utilities and manufacturers publish their own lists:
| Source | Ratings | Note |
|---|---|---|
| IEC 60076-1 | R10 series: 100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1,000 kVA and on | Preferred values up to 20 MVA |
| EU Regulation 548/2014 | 25 kVA and below, 50, 100, 160, 250, 315, 400, 500, 630, 800, 1,000, 1,250, 1,600, 2,000, 2,500 and 3,150 kVA | Rows of its loss tables; ratings in between are interpolated |
| PEA, Thailand | Three-phase 50, 100, 160 and 250 kVA; single-phase 30 kVA | The sizes PEA registers for its own network (PEA-TRAN-001, 2024) |
| EGAT No. 5 label, Thailand | 50 to 2,500 kVA, three-phase, oil-immersed and dry type, up to 36 kV | A voluntary efficiency label |
| Saudi Energy | Pole-mounted 50, 100, 200 and 300 kVA; pad-mounted 300, 500, 1,000 and 1,500 kVA | Specification 51-SDMS-02 (2010 edition), 13.8 and 33 kV networks; check the current revision |
| Thai Trafo (manufacturer) | Oil-immersed 50–10,000 kVA up to 33 kV; cast-resin 100–3,150 kVA; power transformers from 5 MVA | As published by Thai Trafo Manufacturing |
So “how many sizes” depends on who sets the list: the utility that connects the site, the tender specification or the manufacturer’s range. The kVA calculator rounds up to the next common rating.
Types of distribution transformer
Oil-immersed, hermetically sealed
IEC 60076 · liquid-immersed
The tank is completely filled and sealed; its corrugated walls take up the oil’s expansion (Siemens Energy), which keeps the oil sealed from the air.
Outdoor substations and plant rooms, and units on poles or pads.
Oil-immersed, with conservator
IEC 60076 · liquid-immersed
An expansion vessel above the tank takes up the oil’s expansion; it is usually fitted with a breather that dries the air drawn in.
Distribution transformers and larger power transformers.
Cast-resin dry type
IEC 60076-11 · AN or AF
The windings are cast in epoxy resin and cooled by air, with no liquid.
Indoor electrical rooms in buildings, hotels and hospitals — see oil-immersed or cast-resin?
Where the room is exposed to moisture or dust, an enclosure with a suitable IP rating protects it.
Completely self-protected (CSP)
Pole-mounted · oil-immersed
Carries its own protection: a primary surge arrester, internal primary fuses and a secondary circuit breaker (Eaton).
Overhead distribution lines, without separately mounted protective devices.
Pad-mounted
IEEE C57.12.34 · up to 10 MVA, 34.5 kV
A self-cooled, liquid-immersed unit in a closed compartment cabinet on a concrete pad, fed by underground cable.
Underground distribution networks; the IEEE standard covers 60 Hz units.
Power transformer
IEC 60076 · from 5 MVA at Thai Trafo
Larger units for utility and industrial substations, built to the utility’s or the project’s specification.
Feeding medium-voltage networks and large plants.
How oil-immersed and cast-resin units compare on fire, coastal sites, maintenance and cost: oil-immersed or cast-resin?
Voltage and frequency by country
The primary voltage follows the utility network and the frequency follows the country. Published figures:
| Utility | Medium voltage | Low voltage | Frequency |
|---|---|---|---|
| MEA, Thailand | 12 and 24 kV; 69 and 115 kV above | 230/400 V | 50 Hz |
| PEA, Thailand | 22 and 33 kV (single-phase 19 and 22 kV); 69, 115 and 230 kV above | 380/220 V in its regulation; 416/240 V in its transformer specification | 50 Hz |
| DEWA, Dubai (Regulations, 2017 edition) | 11 kV distribution | 230/400 V ±10% | 50 Hz |
| Abu Dhabi | 33, 22 and 11 kV | 400/230 V | 50 Hz |
| Saudi Arabia | 13.8, 33 and 69 kV standard; 11 and 34.5 kV non-standard | 400/230, 380/220 and 220/127 V | 60 Hz |
- Saudi Arabia runs at 60 Hz (Saudi Energy), so state the frequency in every enquiry.
- Low-voltage figures differ even between documents of one utility, so take the values from the connection documents for the site.
- The Saudi figures come from the Distribution Code as quoted in the regulator’s consultation draft on power quality, and from Saudi Energy’s connection standards.
Cooling classes: ONAN, ONAF, AN and AF
IEC 60076-2 names the cooling of a liquid-immersed transformer with four letters: the liquid inside, how it moves, the medium outside, and how that moves.
| Letter | Position | Meaning |
|---|---|---|
| O | 1 · liquid | Mineral oil or synthetic liquid with a fire point of 300 °C or below |
| K | 1 · liquid | Liquid with a fire point above 300 °C, such as a natural ester |
| L | 1 · liquid | Liquid with no measurable fire point |
| N | 2 · liquid flow | Natural flow through the cooler and the windings |
| F | 2 · liquid flow | Pumped through the cooler |
| D | 2 · liquid flow | Pumped and directed into the windings |
| A or W | 3 · outside medium | Air or water |
| N or F | 4 · outside flow | Natural convection, or fans and pumps |
- Oil warmed by the windings rises to the top of the tank
- In the radiators it cools, sinks and returns to the bottom of the tank
- Air flows past the radiators by natural convection (ONAN)
- Fans blow air through the radiators (ONAF)
- ONAN/ONAF: fans switched on at high loading raise the rating, and the rating plate gives both, for example ONAN/ONAF 70/100% (IEC 60076-1).
- KNAN: the same with a less-flammable liquid. IEC 62770 requires a fire point above 300 °C for natural esters; Cargill quotes 360 °C for its FR3 ester and 165 °C for mineral oil.
- Dry type (IEC 60076-11): AN with natural air, AF with fans, or AN/AF with both ratings (Fuji Electric).
Temperature rise and hot climates
IEC 60076-1 assumes a site up to 1,000 m above sea level, with cooling air of at most 40 °C at any time, 30 °C as the monthly average of the hottest month and 20 °C as the yearly average. Under those conditions IEC 60076-2 allows an oil-immersed transformer with conventional (class 105 °C) solid insulation and mineral oil a rise of 60 K in the top oil, 65 K in the average winding (ON and OF cooling) and 78 K at the winding hot spot.
For a hotter site, IEC 60076-2 lowers all these limits by the excess temperature, so the transformer gets more cooling:
| Yearly average | Monthly average | Maximum | Correction |
|---|---|---|---|
| 20 °C | 30 °C | 40 °C | 0 K |
| 25 °C | 35 °C | 45 °C | −5 K |
| 30 °C | 40 °C | 50 °C | −10 K |
| 35 °C | 45 °C | 55 °C | −15 K |
- Above 1,000 m the limits fall by 1 K for every 400 m with natural air cooling, and every 250 m with fans.
- State the site’s maximum, monthly-average and yearly-average temperatures and its altitude in the enquiry, especially for hot sites.
- Dry-type transformers follow IEC 60076-11, which sets winding temperature-rise limits by the thermal class of the insulation; the data sheet states the class, for example class F (Fuji Electric). Limits for other insulation classes are in the standard.
Vector group: what Dyn11 means
The vector group gives the winding connections and the phase shift between them (IEC 60076-1). Capital letters are the high-voltage winding and small letters the low-voltage one: D or d delta, Y or y star, Z or z zigzag, and N or n a neutral brought out. The number is a clock: with the high-voltage phasor at 12 o’clock, it is the hour the low-voltage phasor points to, each hour being 30°.
- D: the high-voltage winding in delta; its first phase points to 12 o’clock
- y: the low-voltage winding in star
- n: the star point brought out as the neutral, for single-phase loads
- 11: the low-voltage phasor points to 11 o’clock; it lags the high-voltage one by 330°, which is a lead of 30°
- IEC 60076-1 uses Dyn11 as its example: a 20 kV delta winding and a 400 V star winding with the neutral brought out.
- PEA’s specification for its three-phase distribution transformers calls for Dyn11.
- To run a new transformer in parallel with an existing one, give the existing unit’s rating, voltage ratio, tappings, load loss and impedance in the enquiry (IEC 60076-1, Annex A); parallel operation needs matching impedance.
Tap changers
Taps change the turns ratio to suit the actual network voltage. IEC 60076-1 defines two kinds:
- De-energized tap changer (DETC), also called off-circuit: operated only with the transformer switched off. A frequent range is ±2 × 2.5% in five positions, as on Fuji Electric’s cast-resin data sheet, where it is a selectable option.
- On-load tap changer (OLTC): changes taps with the transformer energized or on load, where the voltage must be regulated in service.
- Tap changers follow IEC 60214-1. The enquiry states which kind, which winding is tapped, and the number and size of the steps (IEC 60076-1, Annex A).
Losses and efficiency
A transformer has two losses: no-load loss in the core, whenever it is energized, and load loss in the windings, which rises with the square of the current. The transformer loss calculator shows what they cost over a year. Limits come from regulation, the utility or the tender:
- European Union: Regulation (EU) 548/2014, amended by 2019/1783, sets maximum losses for transformers placed on the EU market; Tier 2 has applied since 1 July 2021.
- Thailand: TIS 384 Part 20-2567 is the same as IEC TS 60076-20, which rates efficiency with a peak efficiency index (PEI), and which TISI lists as a general standard (not a compulsory one at the time of writing). EGAT’s No. 5 label for distribution transformers of 50–2,500 kVA is voluntary, and uses PEA’s loss limits for small oil-immersed units.
- Utilities: PEA and Saudi Energy publish maximum losses for transformers on their networks; the Saudi specification says that transformers with higher losses will be rejected.
- Tolerance: IEC 60076-1 accepts measured total losses up to 10% above the guaranteed value, and a component loss up to 15% above its own guaranteed value as long as the total stays within that 10%, unless the enquiry sets other limits.
EU maximum losses (Tier 2, as adopted in 2014)
| Rating | Liquid-immersed: load / no-load | Dry type: load / no-load |
|---|---|---|
| 100 kVA | 1,250 W / 130 W | 1,800 W / 252 W |
| 250 kVA | 2,350 W / 270 W | 3,400 W / 468 W |
| 400 kVA | 3,250 W / 387 W | 4,500 W / 675 W |
| 630 kVA | 4,600 W / 540 W | 7,100 W / 990 W |
| 1,000 kVA | 7,600 W / 693 W | 9,000 W / 1,395 W |
| 2,500 kVA | 18,500 W / 1,575 W | 19,000 W / 2,790 W |
Three-phase units with one winding up to 24 kV and the other up to 1.1 kV. With a 36 kV winding the limits rise by 15% for no-load and 10% for load losses.
Utility limits in Thailand and Saudi Arabia
| Rating | Specification | No-load loss | Load loss |
|---|---|---|---|
| 50 kVA | PEA, 22 kV | 110 W | 875 W |
| 100 kVA | PEA, 22 kV | 180 W | 1,450 W |
| 160 kVA | PEA, 22 kV | 260 W | 2,000 W |
| 250 kVA | PEA, 22 kV | 360 W | 2,750 W |
| 100 kVA | Saudi Energy 51-SDMS-02 | 250 W | 1,500 W |
| 300 kVA | Saudi Energy 51-SDMS-02 | 520 W | 3,200 W |
| 500 kVA | Saudi Energy 51-SDMS-02 | 750 W | 4,700 W |
| 1,000 kVA | Saudi Energy 51-SDMS-02 | 1,100 W | 9,000 W |
| 1,500 kVA | Saudi Energy 51-SDMS-02 | 1,700 W | 14,000 W |
PEA allows higher no-load losses at 33 kV, for example 260 W at 100 kVA, and states load losses at 75 °C. The Saudi figures come from the 2010 edition of 51-SDMS-02; check the current revision.
Short-circuit impedance
The impedance on the rating plate sets the fault current on the low-voltage side and the voltage drop under load. PEA specifies 4% for its three-phase 50–250 kVA units. IEC 60076-1 accepts a measured impedance within ±10% of the specified value when that value is below 10%. The IEC 60076-5 minimum values and a fault-current estimate are in the short-circuit calculator.
Where each type is used
Typical choices from the sections above; the design, the utility and the tender decide.
| Site | Common choice | Points to specify |
|---|---|---|
| Office, hotel or hospital building | Cast-resin dry type in an indoor electrical room | Environmental, climatic and fire classes (IEC 60076-11); room ventilation; enclosure IP rating |
| Factory | Oil-immersed in an outdoor substation, or cast-resin in a plant room | Motors and drives in the load; ONAN or ONAF; loss limits |
| Coastal or island site | Either type, specified for the site | Tank corrosion protection (ISO 12944 C4 or C5) and bushing creepage (IEC TS 60815) — see coastal sites |
| Overhead utility network | CSP or other pole-mounted units | The utility’s own specification and sizes |
| Underground network | Pad-mounted units | Cable connections and the utility’s requirements |
| Utility or industrial substation | Power transformer | Tap changer, cooling and the utility’s specification |
Checklist: what to specify
IEC 60076-1 (Annex A) lists what a purchaser states in an enquiry. For a distribution transformer the main points are:
- Standards to follow (IEC 60076, IEC 60076-11 for dry type, or the utility’s specification) and the loss requirement
- Rated power (kVA), number of units, and single- or three-phase
- Rated voltage of each winding, frequency (50 or 60 Hz) and highest voltage for equipment (Um)
- Oil-immersed (mineral oil or ester) or dry type, indoor or outdoor, and the enclosure IP rating for dry type
- Cooling: ONAN, ONAF, AN or AF
- Vector group and neutral, for example Dyn11
- Tappings: off-circuit or on-load, range and steps, for example ±2 × 2.5%
- Short-circuit impedance, and the data of any transformer it will run in parallel with
- Site: altitude, maximum, monthly and yearly temperatures, coastal or polluted air
- Terminals (bushings or cable boxes) and accessories
- Size and weight limits for transport and access, and the tests and documents required
Not sure of the rating? Start with the kVA calculator, compare offers with the loss calculator and check the switchboard with the short-circuit calculator.
Read more: Thai Trafo transformers. AURIFORTH is an authorized partner of Thai Trafo Manufacturing in Thailand. Export to the UAE, Saudi Arabia and the Maldives is quoted from Thailand.
Sources
Compiled in November 2026 from the standards, regulations, utility documents and manufacturers’ data below. IEC standards are sold by the IEC.
- IEC 60076-1:2011 Power transformers – General
- IEC 60076-2:2011 Temperature rise for liquid-immersed transformers (preview)
- IEC 60076-11:2018 Dry-type transformers
- IEC TS 60076-20:2017 Energy efficiency
- Regulation (EU) No 548/2014, Annex I: maximum losses (as adopted)
- Regulation (EU) No 548/2014, Article 2: definitions
- Regulation (EU) 2019/1783 amending Regulation 548/2014
- IEEE C57.12.34: pad-mounted three-phase distribution transformers
- Siemens Energy: fluid-immersed distribution transformers
- Eaton: single-phase overhead transformers, CSP (catalogue CA201001EN)
- Cargill: FR3 natural ester fluid, technical details
- Fuji Electric: cast-resin transformer data sheet
- Thai Trafo Manufacturing: products
- MEA grid connection code (2015)
- PEA regulation on electricity use and services (2019)
- PEA-TRAN-001: product evaluation of distribution transformers (2024)
- TISI: TIS 384 Part 1-2567 power transformers
- TISI: TIS 384 Part 20-2567 energy efficiency
- EGAT: No. 5 label handbook for distribution transformers (2026)
- DEWA Regulations for Electrical Installations (2017)
- DEWA power supply guidelines for major projects (2017)
- Abu Dhabi Department of Energy: Electricity Supply Regulations (2020)
- Abu Dhabi Department of Energy: annual technical report 2021
- SERA: draft power quality rules quoting the Saudi Distribution Code (draft; the Distribution Code itself was not available)
- Saudi Electricity Company: connection standards for battery storage
- Saudi Electricity Company: 51-SDMS-02 distribution transformers (2010 edition)
- Saudi Electricity Company: FAQ on voltage and frequency
General guidance only. Your project specification, applicable codes and standards, utility requirements and the manufacturer’s documents take precedence.