Electrical

Distribution
transformers.

How a distribution transformer works and how to describe the one you need: its kVA rating, type, cooling, voltages, vector group, tap changer and losses, with the standards and utility documents behind each figure.

Key points

  • kVA is apparent power. For three phases, kVA = √3 × voltage × current ÷ 1,000: a 1,000 kVA transformer at 400 V carries about 1,443 A.
  • IEC 60076-1 prefers ratings from the R10 series (100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1,000 kVA and on), but each utility keeps its own list.
  • Oil-immersed units suit outdoor substations, cast-resin dry-type units suit indoor rooms, and CSP and pad-mounted units serve utility networks.
  • ONAN means oil, natural oil flow, air, natural air flow; ONAF adds fans. Dyn11 is a common distribution connection, and PEA specifies it.
  • Losses are limited by regulation, the utility or the tender: EU Tier 2 since July 2021, PEA and Saudi Energy (formerly Saudi Electricity Company) specifications, and Thailand’s voluntary No. 5 label.
Where distribution transformers stand: on a pole, on a pad, in a building, beside a factory and in a utility substation

Simplified drawing, not to scale.

  1. Pole-mounted (CSP) transformer on an overhead medium-voltage line, with a low-voltage line to houses
  2. Pad-mounted transformer on the ground, fed by an underground cable
  3. Cast-resin transformer in an indoor electrical room of a building
  4. Oil-immersed transformer outdoors beside a factory
  5. Power transformer in a utility substation, fed from a high-voltage line
  6. Medium-voltage network: overhead lines and underground cables

What a distribution transformer does

A transformer changes the voltage and keeps the frequency. A distribution transformer takes the medium voltage of the utility network — in Thailand 22 or 33 kV with PEA, 12 or 24 kV with MEA — and steps it down to the low voltage that buildings and machines use, such as 400/230 V. Siemens Energy describes its liquid-immersed distribution transformers as typically up to 36 kV on the primary side and 250–800 V on the secondary side.

The EU ecodesign regulation calls a transformer with a highest voltage for equipment above 1.1 kV and up to 36 kV, rated from 5 kVA to below 40 MVA, a medium power transformer, and sets maximum losses for it.

Inside an oil-immersed transformer (A) and a cast-resin dry-type transformer (B)

Schematic, not to scale.

  1. Core: carries the magnetic field that links the windings
  2. Low-voltage winding, next to the core
  3. High-voltage winding, around the low-voltage winding
  4. Insulating liquid (mineral oil or an ester): insulates the windings and carries their heat to the tank
  5. Corrugated wall: in a hermetically sealed tank it flexes as the oil expands and contracts (Siemens Energy)
  6. High-voltage bushing
  7. Low-voltage bushing
  8. Off-circuit tap changer handle, turned only with the transformer switched off
  9. High-voltage coil cast in epoxy resin, cooled by air
  10. Tapping links, changed only with the transformer switched off
  11. Low-voltage terminals
  12. Fans for forced-air cooling (AF), where fitted

What kVA means

A transformer is rated by its rated power in kVA: the apparent power that, with the rated voltage, sets the rated current (IEC 60076-1). Apparent power counts the whole current, whatever the power factor of the load, so the rating is given in kVA rather than kW.

Apparent, real and reactive power, and the voltage and current of a three-phase line
  1. Real power (kW): what the loads turn into work and heat
  2. Reactive power (kVAr), drawn by motors and other inductive loads
  3. Apparent power (kVA): what the transformer must carry
  4. Power factor = kW ÷ kVA, the cosine of this angle
  5. Voltage between two lines (U), for example 400 V
  6. Current in each line (I)
  • Three-phase: kVA = √3 × U (V) × I (A) ÷ 1,000. The other way round, full-load current I = kVA × 1,000 ÷ (√3 × U).
  • From kW: kVA = kW ÷ power factor. A load of 800 kW at a power factor of 0.85 needs about 941 kVA before any spare capacity.
  • On the rating plate: IEC 60076-1 requires the rated power, frequency, rated voltages and tapping range, rated currents, vector group, short-circuit impedance and type of cooling, among others.
  • Rated voltage is a no-load value (IEC 60076-1). That is why a transformer for a 400/230 V network can show 416/240 V on its plate, as in PEA’s specification for its own distribution transformers.
RatingFull-load current at 400 V
100 kVA144 A
160 kVA231 A
250 kVA361 A
400 kVA577 A
630 kVA909 A
800 kVA1,155 A
1,000 kVA1,443 A
1,250 kVA1,804 A
1,600 kVA2,309 A
2,000 kVA2,887 A
2,500 kVA3,608 A

To size a transformer from the connected load, demand factor and power factor, use the transformer kVA calculator.

Standard kVA ratings

There is no single list. IEC 60076-1 recommends that ratings up to 20 MVA be taken from the R10 series of preferred numbers — 100, 125, 160, 200, 250, 315, 400, 500, 630, 800 and 1,000 kVA, and on through the same series — and notes that national practices may differ. Regulators, utilities and manufacturers publish their own lists:

SourceRatingsNote
IEC 60076-1R10 series: 100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1,000 kVA and onPreferred values up to 20 MVA
EU Regulation 548/201425 kVA and below, 50, 100, 160, 250, 315, 400, 500, 630, 800, 1,000, 1,250, 1,600, 2,000, 2,500 and 3,150 kVARows of its loss tables; ratings in between are interpolated
PEA, ThailandThree-phase 50, 100, 160 and 250 kVA; single-phase 30 kVAThe sizes PEA registers for its own network (PEA-TRAN-001, 2024)
EGAT No. 5 label, Thailand50 to 2,500 kVA, three-phase, oil-immersed and dry type, up to 36 kVA voluntary efficiency label
Saudi EnergyPole-mounted 50, 100, 200 and 300 kVA; pad-mounted 300, 500, 1,000 and 1,500 kVASpecification 51-SDMS-02 (2010 edition), 13.8 and 33 kV networks; check the current revision
Thai Trafo (manufacturer)Oil-immersed 50–10,000 kVA up to 33 kV; cast-resin 100–3,150 kVA; power transformers from 5 MVAAs published by Thai Trafo Manufacturing

So “how many sizes” depends on who sets the list: the utility that connects the site, the tender specification or the manufacturer’s range. The kVA calculator rounds up to the next common rating.

Types of distribution transformer

  • Oil-immersed, hermetically sealed

    IEC 60076 · liquid-immersed

    The tank is completely filled and sealed; its corrugated walls take up the oil’s expansion (Siemens Energy), which keeps the oil sealed from the air.

    Outdoor substations and plant rooms, and units on poles or pads.

  • Oil-immersed, with conservator

    IEC 60076 · liquid-immersed

    An expansion vessel above the tank takes up the oil’s expansion; it is usually fitted with a breather that dries the air drawn in.

    Distribution transformers and larger power transformers.

  • Cast-resin dry type

    IEC 60076-11 · AN or AF

    The windings are cast in epoxy resin and cooled by air, with no liquid.

    Indoor electrical rooms in buildings, hotels and hospitals — see oil-immersed or cast-resin?

    Where the room is exposed to moisture or dust, an enclosure with a suitable IP rating protects it.

  • Completely self-protected (CSP)

    Pole-mounted · oil-immersed

    Carries its own protection: a primary surge arrester, internal primary fuses and a secondary circuit breaker (Eaton).

    Overhead distribution lines, without separately mounted protective devices.

  • Pad-mounted

    IEEE C57.12.34 · up to 10 MVA, 34.5 kV

    A self-cooled, liquid-immersed unit in a closed compartment cabinet on a concrete pad, fed by underground cable.

    Underground distribution networks; the IEEE standard covers 60 Hz units.

  • Power transformer

    IEC 60076 · from 5 MVA at Thai Trafo

    Larger units for utility and industrial substations, built to the utility’s or the project’s specification.

    Feeding medium-voltage networks and large plants.

How oil-immersed and cast-resin units compare on fire, coastal sites, maintenance and cost: oil-immersed or cast-resin?

Voltage and frequency by country

The primary voltage follows the utility network and the frequency follows the country. Published figures:

UtilityMedium voltageLow voltageFrequency
MEA, Thailand12 and 24 kV; 69 and 115 kV above230/400 V50 Hz
PEA, Thailand22 and 33 kV (single-phase 19 and 22 kV); 69, 115 and 230 kV above380/220 V in its regulation; 416/240 V in its transformer specification50 Hz
DEWA, Dubai (Regulations, 2017 edition)11 kV distribution230/400 V ±10%50 Hz
Abu Dhabi33, 22 and 11 kV400/230 V50 Hz
Saudi Arabia13.8, 33 and 69 kV standard; 11 and 34.5 kV non-standard400/230, 380/220 and 220/127 V60 Hz
  • Saudi Arabia runs at 60 Hz (Saudi Energy), so state the frequency in every enquiry.
  • Low-voltage figures differ even between documents of one utility, so take the values from the connection documents for the site.
  • The Saudi figures come from the Distribution Code as quoted in the regulator’s consultation draft on power quality, and from Saudi Energy’s connection standards.

Cooling classes: ONAN, ONAF, AN and AF

IEC 60076-2 names the cooling of a liquid-immersed transformer with four letters: the liquid inside, how it moves, the medium outside, and how that moves.

LetterPositionMeaning
O1 · liquidMineral oil or synthetic liquid with a fire point of 300 °C or below
K1 · liquidLiquid with a fire point above 300 °C, such as a natural ester
L1 · liquidLiquid with no measurable fire point
N2 · liquid flowNatural flow through the cooler and the windings
F2 · liquid flowPumped through the cooler
D2 · liquid flowPumped and directed into the windings
A or W3 · outside mediumAir or water
N or F4 · outside flowNatural convection, or fans and pumps
Oil circulation in an ONAN transformer (A) and an ONAF transformer with fans (B)
  1. Oil warmed by the windings rises to the top of the tank
  2. In the radiators it cools, sinks and returns to the bottom of the tank
  3. Air flows past the radiators by natural convection (ONAN)
  4. Fans blow air through the radiators (ONAF)
  • ONAN/ONAF: fans switched on at high loading raise the rating, and the rating plate gives both, for example ONAN/ONAF 70/100% (IEC 60076-1).
  • KNAN: the same with a less-flammable liquid. IEC 62770 requires a fire point above 300 °C for natural esters; Cargill quotes 360 °C for its FR3 ester and 165 °C for mineral oil.
  • Dry type (IEC 60076-11): AN with natural air, AF with fans, or AN/AF with both ratings (Fuji Electric).

Temperature rise and hot climates

IEC 60076-1 assumes a site up to 1,000 m above sea level, with cooling air of at most 40 °C at any time, 30 °C as the monthly average of the hottest month and 20 °C as the yearly average. Under those conditions IEC 60076-2 allows an oil-immersed transformer with conventional (class 105 °C) solid insulation and mineral oil a rise of 60 K in the top oil, 65 K in the average winding (ON and OF cooling) and 78 K at the winding hot spot.

For a hotter site, IEC 60076-2 lowers all these limits by the excess temperature, so the transformer gets more cooling:

Yearly averageMonthly averageMaximumCorrection
20 °C30 °C40 °C0 K
25 °C35 °C45 °C−5 K
30 °C40 °C50 °C−10 K
35 °C45 °C55 °C−15 K
  • Above 1,000 m the limits fall by 1 K for every 400 m with natural air cooling, and every 250 m with fans.
  • State the site’s maximum, monthly-average and yearly-average temperatures and its altitude in the enquiry, especially for hot sites.
  • Dry-type transformers follow IEC 60076-11, which sets winding temperature-rise limits by the thermal class of the insulation; the data sheet states the class, for example class F (Fuji Electric). Limits for other insulation classes are in the standard.

Vector group: what Dyn11 means

The vector group gives the winding connections and the phase shift between them (IEC 60076-1). Capital letters are the high-voltage winding and small letters the low-voltage one: D or d delta, Y or y star, Z or z zigzag, and N or n a neutral brought out. The number is a clock: with the high-voltage phasor at 12 o’clock, it is the hour the low-voltage phasor points to, each hour being 30°.

The vector group Dyn11 shown on two clock faces
  1. D: the high-voltage winding in delta; its first phase points to 12 o’clock
  2. y: the low-voltage winding in star
  3. n: the star point brought out as the neutral, for single-phase loads
  4. 11: the low-voltage phasor points to 11 o’clock; it lags the high-voltage one by 330°, which is a lead of 30°
  • IEC 60076-1 uses Dyn11 as its example: a 20 kV delta winding and a 400 V star winding with the neutral brought out.
  • PEA’s specification for its three-phase distribution transformers calls for Dyn11.
  • To run a new transformer in parallel with an existing one, give the existing unit’s rating, voltage ratio, tappings, load loss and impedance in the enquiry (IEC 60076-1, Annex A); parallel operation needs matching impedance.

Tap changers

Taps change the turns ratio to suit the actual network voltage. IEC 60076-1 defines two kinds:

  • De-energized tap changer (DETC), also called off-circuit: operated only with the transformer switched off. A frequent range is ±2 × 2.5% in five positions, as on Fuji Electric’s cast-resin data sheet, where it is a selectable option.
  • On-load tap changer (OLTC): changes taps with the transformer energized or on load, where the voltage must be regulated in service.
  • Tap changers follow IEC 60214-1. The enquiry states which kind, which winding is tapped, and the number and size of the steps (IEC 60076-1, Annex A).

Losses and efficiency

A transformer has two losses: no-load loss in the core, whenever it is energized, and load loss in the windings, which rises with the square of the current. The transformer loss calculator shows what they cost over a year. Limits come from regulation, the utility or the tender:

  • European Union: Regulation (EU) 548/2014, amended by 2019/1783, sets maximum losses for transformers placed on the EU market; Tier 2 has applied since 1 July 2021.
  • Thailand: TIS 384 Part 20-2567 is the same as IEC TS 60076-20, which rates efficiency with a peak efficiency index (PEI), and which TISI lists as a general standard (not a compulsory one at the time of writing). EGAT’s No. 5 label for distribution transformers of 50–2,500 kVA is voluntary, and uses PEA’s loss limits for small oil-immersed units.
  • Utilities: PEA and Saudi Energy publish maximum losses for transformers on their networks; the Saudi specification says that transformers with higher losses will be rejected.
  • Tolerance: IEC 60076-1 accepts measured total losses up to 10% above the guaranteed value, and a component loss up to 15% above its own guaranteed value as long as the total stays within that 10%, unless the enquiry sets other limits.

EU maximum losses (Tier 2, as adopted in 2014)

RatingLiquid-immersed: load / no-loadDry type: load / no-load
100 kVA1,250 W / 130 W1,800 W / 252 W
250 kVA2,350 W / 270 W3,400 W / 468 W
400 kVA3,250 W / 387 W4,500 W / 675 W
630 kVA4,600 W / 540 W7,100 W / 990 W
1,000 kVA7,600 W / 693 W9,000 W / 1,395 W
2,500 kVA18,500 W / 1,575 W19,000 W / 2,790 W

Three-phase units with one winding up to 24 kV and the other up to 1.1 kV. With a 36 kV winding the limits rise by 15% for no-load and 10% for load losses.

Utility limits in Thailand and Saudi Arabia

RatingSpecificationNo-load lossLoad loss
50 kVAPEA, 22 kV110 W875 W
100 kVAPEA, 22 kV180 W1,450 W
160 kVAPEA, 22 kV260 W2,000 W
250 kVAPEA, 22 kV360 W2,750 W
100 kVASaudi Energy 51-SDMS-02250 W1,500 W
300 kVASaudi Energy 51-SDMS-02520 W3,200 W
500 kVASaudi Energy 51-SDMS-02750 W4,700 W
1,000 kVASaudi Energy 51-SDMS-021,100 W9,000 W
1,500 kVASaudi Energy 51-SDMS-021,700 W14,000 W

PEA allows higher no-load losses at 33 kV, for example 260 W at 100 kVA, and states load losses at 75 °C. The Saudi figures come from the 2010 edition of 51-SDMS-02; check the current revision.

Short-circuit impedance

The impedance on the rating plate sets the fault current on the low-voltage side and the voltage drop under load. PEA specifies 4% for its three-phase 50–250 kVA units. IEC 60076-1 accepts a measured impedance within ±10% of the specified value when that value is below 10%. The IEC 60076-5 minimum values and a fault-current estimate are in the short-circuit calculator.

Where each type is used

Typical choices from the sections above; the design, the utility and the tender decide.

SiteCommon choicePoints to specify
Office, hotel or hospital buildingCast-resin dry type in an indoor electrical roomEnvironmental, climatic and fire classes (IEC 60076-11); room ventilation; enclosure IP rating
FactoryOil-immersed in an outdoor substation, or cast-resin in a plant roomMotors and drives in the load; ONAN or ONAF; loss limits
Coastal or island siteEither type, specified for the siteTank corrosion protection (ISO 12944 C4 or C5) and bushing creepage (IEC TS 60815) — see coastal sites
Overhead utility networkCSP or other pole-mounted unitsThe utility’s own specification and sizes
Underground networkPad-mounted unitsCable connections and the utility’s requirements
Utility or industrial substationPower transformerTap changer, cooling and the utility’s specification

Checklist: what to specify

IEC 60076-1 (Annex A) lists what a purchaser states in an enquiry. For a distribution transformer the main points are:

  • Standards to follow (IEC 60076, IEC 60076-11 for dry type, or the utility’s specification) and the loss requirement
  • Rated power (kVA), number of units, and single- or three-phase
  • Rated voltage of each winding, frequency (50 or 60 Hz) and highest voltage for equipment (Um)
  • Oil-immersed (mineral oil or ester) or dry type, indoor or outdoor, and the enclosure IP rating for dry type
  • Cooling: ONAN, ONAF, AN or AF
  • Vector group and neutral, for example Dyn11
  • Tappings: off-circuit or on-load, range and steps, for example ±2 × 2.5%
  • Short-circuit impedance, and the data of any transformer it will run in parallel with
  • Site: altitude, maximum, monthly and yearly temperatures, coastal or polluted air
  • Terminals (bushings or cable boxes) and accessories
  • Size and weight limits for transport and access, and the tests and documents required

Not sure of the rating? Start with the kVA calculator, compare offers with the loss calculator and check the switchboard with the short-circuit calculator.

Read more: Thai Trafo transformers. AURIFORTH is an authorized partner of Thai Trafo Manufacturing in Thailand. Export to the UAE, Saudi Arabia and the Maldives is quoted from Thailand.

Sources

Compiled in November 2026 from the standards, regulations, utility documents and manufacturers’ data below. IEC standards are sold by the IEC.

General guidance only. Your project specification, applicable codes and standards, utility requirements and the manufacturer’s documents take precedence.

Glossary of terms

Questions

Frequently asked.

How many standard sizes do transformers come in?

There is no single list. IEC 60076-1 prefers the R10 series (100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1,000 kVA and on), and each utility keeps its own: PEA registers three-phase 50, 100, 160 and 250 kVA units for its network, and Saudi Energy (formerly Saudi Electricity Company) specifies 50–300 kVA pole-mounted and 300–1,500 kVA pad-mounted units.

How do I find the kVA of a transformer?

Read the rated power on the rating plate. From the rated current: kVA = √3 × voltage × current ÷ 1,000, for example 1.732 × 400 V × 1,443 A ÷ 1,000 ≈ 1,000 kVA. A measured current gives the load, not the capacity. To size a new transformer, use the kVA calculator.

What is the difference between kVA and kW?

kVA is apparent power, which sets the current the transformer carries; kW is the real power the loads use. kW = kVA × power factor, so 1,000 kVA at a power factor of 0.8 supplies 800 kW.

What does ONAN mean?

Oil Natural Air Natural: mineral oil (or a liquid with a fire point up to 300 °C) circulating naturally, cooled by air moving naturally (IEC 60076-2). ONAF adds fans; KNAN uses a less-flammable liquid such as a natural ester.

What does Dyn11 mean?

A delta high-voltage winding (D), a star low-voltage winding (y) with its neutral brought out (n), and a phase shift of 11 on the clock: the low-voltage side leads by 30°. It is a common connection for distribution transformers, and PEA specifies it.

What are the advantages of cast-resin transformers?

There is no liquid to leak or burn, so they suit indoor rooms in buildings, hotels and hospitals, and fire class F1 units are designed for restricted flammability. They usually cost more than oil-immersed units of the same rating. See oil-immersed or cast-resin?

What is a CSP transformer?

A completely self-protected transformer for overhead lines. It has a primary surge arrester, internal primary fuses and a secondary circuit breaker built in, so no separate protective devices are mounted (Eaton).

Keep reading

Related.

  • Solution

    Electrical equipment & works

    Transformers, switchgear, power cables and transmission products from established manufacturers — supplied for projects in Thailand and exported to the UAE, Saudi Arabia and the Maldives, with installation and integration where included in the agreed scope. Diesel generators and the rest of TECHNOPOWER’s range are offered as the general reseller of TECHNOPOWER (FZC).

    See the solution: Electrical equipment & works
  • Authorized Thai Trafo partner

    Transformers from Thai Trafo.

    Distribution and power transformers made in Rayong by Thai Trafo Manufacturing — supplied by AURIFORTH as its authorized partner for projects and tenders in Thailand. Export to the UAE, Saudi Arabia and the Maldives is quoted from Thailand, as agreed in each quotation.

    See the products: Transformers from Thai Trafo.
  • Electrical

    Oil-immersed or cast-resin?

    Both types step voltage down for a building or site. The right choice depends on where the transformer stands, the rating you need and what your utility or specification requires.

    Read the guide: Oil-immersed or cast-resin?