Calculator
Transformer loss
and efficiency calculator.
Turn the no-load and load losses in a transformer quotation into efficiency and the energy lost each year — a quick way to compare offers before you order.
An estimate for planning and comparing offers, at one steady loading. The starting values are examples, not a manufacturer’s figures — enter the losses from the quotation or test report of the unit offered.
How the estimate works
- Load loss at this loading = load loss at rated current × (loading ÷ 100)² — it follows the square of the current
- Total loss = no-load loss + load loss at this loading
- Efficiency = output ÷ (output + total loss), where output (kW) = rating × loading × power factor
- Loading of peak efficiency = √(no-load loss ÷ load loss at rated current) × 100 — the loading at which the two losses are equal
- Energy lost per year (kWh) = total loss × hours energised ÷ 1,000, with the loading held at the value entered
- Cost of the losses = energy lost × energy price
Two kinds of loss
A transformer loses energy in two ways. No-load loss, in the core, is drawn whenever the transformer is energised, even with nothing connected. Load loss, in the windings, depends on the current: at half load it is a quarter of its value at rated current. The manufacturer states both in the quotation and the test report; IEC 60076-1 sets out how they are measured, with the load loss corrected to a reference temperature.
Comparing quotations
A transformer runs for decades, so a lower-priced unit with higher losses can cost more over its life. Compare offers at the same loading and hours, and look at both losses: a transformer that is lightly loaded most of the time gains most from a low no-load loss, one that runs near its rating from a low load loss. Tender specifications often set maximum values for both — see oil-immersed or cast-resin transformers.
Before you rely on the figures
- Use the losses the manufacturer states for the unit offered, with their tolerance, not figures for a different rating or design
- A load that changes through the day has load losses set by its root-mean-square loading, which is higher than the average — entering the average gives a figure that is too low
- Harmonic currents from drives, UPS systems and LED drivers add to the load loss; the estimate leaves them out
- Cooling fans, where fitted, and the losses in the switchgear and cables are not included
Loss limits under EU Tier 2 and in the PEA and Saudi Energy (formerly Saudi Electricity Company) specifications are listed in the distribution transformer guide.
Next, see Thai Trafo transformers or size the transformer, then send your loads and specification for a quotation.
Keep reading
Related.
Authorized Thai Trafo partner
Transformers from Thai Trafo.
Distribution and power transformers made in Rayong by Thai Trafo Manufacturing — supplied by AURIFORTH as its authorized partner for projects and tenders in Thailand. Export to the UAE, Saudi Arabia and the Maldives is quoted from Thailand, as agreed in each quotation.
See the products: Transformers from Thai Trafo.Electrical
Oil-immersed or cast-resin?
Both types step voltage down for a building or site. The right choice depends on where the transformer stands, the rating you need and what your utility or specification requires.
Read the guide: Oil-immersed or cast-resin?