Calculator

Transformer
kVA calculator.

Estimate the transformer rating for a building or site from its load — a quick check before you request a quotation.

Your load

Total rated power of the equipment the transformer will supply

Share of the connected load running at the same time — use 1 if unsure

Use 0.85 if not known; higher with power factor correction

Allowance for future load

Estimate

Maximum demand
400 kW
Required capacity
564.7 kVA
Next common rating
630 kVA
Loading at that rating
89.6%
Full-load current, low-voltage side
909.3 A

An estimate for planning and enquiries. The final rating follows the electrical designer’s load calculation, the utility’s requirements and the tender specification.

How the estimate works

  • Maximum demand (kW) = connected load × demand factor
  • Apparent power (kVA) = maximum demand ÷ power factor
  • Required capacity (kVA) = apparent power × (1 + spare capacity)
  • Next common rating = the first rating in the list below at or above the required capacity
  • Full-load current (A) = rating × 1,000 ÷ (√3 × low-voltage side voltage)

Standard transformer sizes

50, 100, 160, 250, 315, 400, 500, 630, 800, 1,000, 1,250, 1,500, 2,000, 2,500 and 3,150 kVA for distribution transformers, and larger units up to 10,000 kVA. Available ratings vary by manufacturer and utility — Thai Trafo builds oil-immersed transformers from 50 to 10,000 kVA and cast-resin units up to 3,150 kVA.

IEC 60076-1 prefers ratings from the R10 series, and each utility keeps its own list; the distribution transformer guide compares them.

When to choose a larger rating

  • Large motors that start directly on line, or lifts and pumps that start often
  • Non-linear loads such as variable speed drives, UPS systems and LED drivers, which add harmonics
  • High ambient temperature or a poorly ventilated room
  • Load growth that is already planned

Next, choose the type — see oil-immersed or cast-resin? — and send your specification for a quotation.

Keep reading

Related.

  • Electrical

    Oil-immersed or cast-resin?

    Both types step voltage down for a building or site. The right choice depends on where the transformer stands, the rating you need and what your utility or specification requires.

    Read the guide: Oil-immersed or cast-resin?
  • Solution

    Electrical equipment & works

    Transformers, switchgear, power cables and transmission products from established manufacturers — supplied for projects in Thailand and exported to the UAE, Saudi Arabia and the Maldives, with installation and integration where included in the agreed scope. Diesel generators and the rest of TECHNOPOWER’s range are offered as the general reseller of TECHNOPOWER (FZC).

    See the solution: Electrical equipment & works

Start your enquiry.

Send your requirement — our sales team replies by email.

sales@auriforth.com