Key points
- Oil-immersed transformers suit outdoor substations and higher ratings, and usually cost less at the same rating.
- Cast-resin dry-type transformers suit indoor electrical rooms in buildings, hotels and other places where fire risk must be kept low.
- On coastal or humid sites, specify the environment as well as the rating — for dry-type units, the IEC 60076-11 classes.
- Utility connection rules and your tender specification come first.
Two ways to insulate and cool a transformer
Every distribution transformer does the same job: it changes the utility’s medium voltage — for example 22 kV or 33 kV in Thailand — to the low voltage your building uses. The two types differ in how the windings are insulated and cooled.
- Oil-immersed — the core and windings sit in a steel tank filled with insulating oil, which carries heat to the tank walls and radiators. Hermetically sealed designs have no conservator and keep air and moisture away from the oil.
- Cast-resin dry-type — the windings are encapsulated in epoxy resin and cooled by air. There is no liquid to leak or burn, and fans can be added for extra cooling capacity.
Where each type fits
| Oil-immersed | Cast-resin dry-type | |
|---|---|---|
| Typical location | Outdoor substations, pad or pole mounting, and plant rooms designed for oil | Indoor electrical rooms in buildings, hotels, hospitals and data centers |
| Fire | Mineral oil is combustible; indoor rooms need fire separation and oil containment as local codes require | Fire class F1 units are designed for restricted flammability and low smoke; no liquid to contain |
| Ratings | Wide range — Thai Trafo builds 50–10,000 kVA up to 33 kV, and power transformers from 5 MVA | Thai Trafo builds cast-resin units up to 3,150 kVA |
| Maintenance | Periodic oil tests, such as breakdown voltage and dissolved gas analysis (DGA), and checks for leaks | Periodic cleaning of dust and deposits, and checks of connections and temperature monitoring |
| Cost | Usually lower purchase cost at the same rating | Usually higher purchase cost; indoors it can save on fire protection and room construction |
Advantages of cast-resin and oil-immersed transformers
- Cast-resin, fire safety: there is no oil to leak or burn, and fire class F1 units are designed for restricted flammability and low smoke, so they suit indoor electrical rooms in buildings, hotels, hospitals and data centers
- Cast-resin, indoor installation: with no liquid to contain, an indoor room can save on fire protection and room construction, which offsets part of the higher purchase cost
- Cast-resin, maintenance: periodic cleaning of dust and deposits, and checks of connections and temperature monitoring, with no oil to test
- Oil-immersed, cost: usually a lower purchase cost at the same rating
- Oil-immersed, ratings and location: a wide range of ratings (Thai Trafo builds 50–10,000 kVA up to 33 kV) for outdoor substations and pad or pole mounting
Coastal and humid sites
Salt air and humidity affect both types. For an oil-immersed unit, specify a tank paint system for the corrosion category of the site — for example C4 or C5 under ISO 12944 — and bushings with a creepage distance suited to the site’s pollution level (IEC TS 60815).
For a cast-resin unit, IEC 60076-11 sets three classes to state in the specification: environmental class E0, E1 or E2 (E2 for frequent condensation or heavy pollution), climatic class C1 or C2, and fire class F0 or F1. Where the room itself is exposed to moisture or dust, an enclosure with a suitable IP rating protects the unit.
Efficiency and losses
A transformer runs for decades, so its losses add up. Tender specifications often set maximum no-load and load losses, or refer to an efficiency standard. State the limits or the standard in your enquiry so the manufacturer can design to them. The distribution transformer guide lists EU and utility loss limits, cooling classes and vector groups.
Utility and specification requirements come first
If the transformer connects to a utility network — PEA or MEA in Thailand, or the local utility in the Maldives — its rating, voltages, vector group and accessories must follow the utility’s requirements. Government tenders add their own specification. Start from those documents; the choice of type usually follows from them.
What to send for a quotation
- Rating (kVA) and quantity
- Primary and secondary voltage, frequency and vector group
- Oil-immersed or cast-resin, indoor or outdoor
- Site conditions — coastal air, altitude and ambient temperature
- Loss limits, tap changer and accessories required
- Delivery location and target date
Not sure of the rating? Estimate it with the transformer kVA calculator.