Calculator

Transformer fault
current calculator.

Estimate the maximum fault current at the main switchboard from the transformer’s rating and impedance — a quick check before you choose breakers and request a quotation.

Your transformer

From the nameplate, or the rating you plan

From the nameplate or datasheet — IEC 60076-5 minimums are 4% up to 630 kVA, 5% to 1,250 kVA and 6% to 2,500 kVA

Estimate

Full-load current, each transformer
1,443.4 A
Fault current from one transformer
28.9 kA
Maximum fault current at the busbar
28.9 kA
Fault level at the busbar
20 MVA

An estimate of the three-phase fault current at the transformer’s low-voltage terminals, for planning and enquiries. Design values come from the electrical designer’s short-circuit study.

How the estimate works

  • Full-load current (A) = rating (kVA) × 1,000 ÷ (√3 × low-voltage side voltage)
  • Fault current from one transformer (kA) = full-load current × 100 ÷ impedance voltage (%) ÷ 1,000 — the three-phase short-circuit current at its low-voltage terminals
  • At the busbar, identical transformers running in parallel all feed the fault, so their currents add
  • Fault level (MVA) = rating (kVA) × 100 ÷ impedance voltage ÷ 1,000, for each transformer on the busbar

Why it is the maximum

The estimate treats the medium-voltage network behind the transformer as infinitely strong and leaves out the cables to the switchboard, so the real current is lower — which makes it a safe figure for choosing breaking capacity at the main switchboard. Two things push the real value up: the voltage factor that IEC 60909 applies to the maximum short-circuit current, and large motors running when the fault happens, which feed current back into it. The electrical designer’s short-circuit study includes both.

Where the impedance comes from

The impedance voltage (uk, also called short-circuit impedance) is on the transformer’s nameplate and test report. IEC 60076-5 gives minimum values of 4% up to 630 kVA, 5% from 631 to 1,250 kVA, 6% from 1,251 to 2,500 kVA and 7% from 2,501 to 6,300 kVA. A lower impedance means a higher fault current; a higher one means more voltage drop under load. Utilities often set the value in their transformer specifications.

Using the result

  • The main breaker and every device at the main switchboard need a breaking capacity at or above the busbar fault current
  • The switchboard busbars need a rated short-time withstand current (Icw) at or above it, for as long as the protection takes to clear the fault
  • Further from the transformer, cable impedance lowers the fault current, so sub-boards can often use lower ratings — confirm with the designer’s study
  • Two transformers in parallel double the fault current at a shared busbar, which is why designers often split the busbar with a bus coupler that stays open in normal operation

Vector groups, tap changers, cooling classes and the rest of a transformer specification are explained in the distribution transformer guide.

Next, see switchgear and switchboards or size the transformer, then send your single-line diagram for a quotation.

Keep reading

Related.

  • Schneider Electric

    Switchgear and circuit breakers.

    Medium-voltage switchgear, circuit breakers and low-voltage distribution from Schneider Electric — supplied for buildings, plants and utility projects in Thailand, and exported to the UAE, Saudi Arabia and the Maldives.

    See the products: Switchgear and circuit breakers.
  • Calculator

    Transformer kVA calculator.

    Estimate the transformer rating for a building or site from its load — a quick check before you request a quotation.

    Open the calculator: Transformer kVA calculator.

Start your enquiry.