Calculator
Motor full-load
current calculator.
Estimate the current a three-phase motor draws at full load and while it starts — a quick check before you choose its circuit breaker, starter and cable, and request a quotation.
An estimate for planning and enquiries, for a three-phase induction motor at its rated voltage and output. The rated current on the nameplate comes first; the protection, starter and cable follow the electrical designer and the manufacturers’ selection tables.
How the estimate works
- Electrical input power (kW) = rated output ÷ efficiency
- Apparent power (kVA) = input power ÷ power factor
- Full-load current (A) = apparent power × 1,000 ÷ (√3 × system voltage)
- Starting current, direct on line (A) = full-load current × starting current ratio
- Starting current, star-delta (A) = starting current direct on line ÷ 3
- Starting kVA = apparent power × starting current ratio — the momentary load the start puts on the transformer
The nameplate comes first
A motor’s rated output is the mechanical power at its shaft, not the power it takes from the supply: the supply also covers the motor’s losses and its reactive power. That is why the current depends on efficiency and power factor as well as on kW. The nameplate states the rated current at each rated voltage — use it where you have it, and this estimate where you only know the kW. IEC 60034-30-1 defines efficiency classes IE1 to IE4 for motors; state the class you need in your enquiry.
Starting current and the supply
Started direct on line, an induction motor draws its locked-rotor current — several times its rated current — until it comes up to speed. The data sheet gives it as a ratio of the rated current (IA/IN). This current causes a momentary voltage drop in the cables and the transformer, which other equipment on the same supply may notice — see the voltage drop calculator.
- Star-delta starting runs the motor up with its windings in star, then switches them to delta: the starting line current and the starting torque fall to about one third of their direct-on-line values, so it suits loads that start lightly
- Soft starters lower the voltage while the motor accelerates, which reduces both the current and the torque during the start
- Variable speed drives raise the frequency and voltage together, so the drive limits the current during the start and the speed can be controlled while the motor runs
Choosing the motor circuit
- The circuit breaker or motor protection must carry the starting current for the length of the start without tripping, and still protect the cable — manufacturers publish selection tables for motor circuits by kW and voltage
- A motor made for 50 Hz is not automatically suitable for 60 Hz: Thailand uses 50 Hz and Saudi Arabia 60 Hz, so state the frequency in your enquiry — see exporting to Saudi Arabia
- Many motors on one switchboard add up: use the transformer kVA calculator for the total demand, and the power factor calculator where their power factor is low
Next, see switchgear and switchboards, then send your motor list and single-line diagram for a quotation.
Keep reading
Related.
Schneider Electric
Switchgear and circuit breakers.
Medium-voltage switchgear, circuit breakers and low-voltage distribution from Schneider Electric — supplied for buildings, plants and utility projects in Thailand, and exported to the UAE, Saudi Arabia and the Maldives.
See the products: Switchgear and circuit breakers.Calculator
Voltage drop calculator.
Estimate the voltage drop on a copper cable run, and the smallest standard size that keeps it within your limit — a quick check before you request a quotation.
Open the calculator: Voltage drop calculator.