Calculator
Voltage drop
calculator.
Estimate the voltage drop on a copper cable run, and the smallest standard size that keeps it within your limit — a quick check before you request a quotation.
An estimate for copper conductors at full operating temperature, for planning and enquiries. The final cable size follows the electrical designer’s calculation and the applicable installation standard.
How the estimate works
- Resistance at operating temperature = resistance at 20 °C × (1 + 0.00393 × (temperature − 20)), from the maximum resistance of stranded copper conductors in IEC 60228
- Voltage drop (V) = b × current × length × (R × power factor + X × sin φ) ÷ 1,000 — with b = √3 for three-phase and 2 for single-phase, R and X in Ω/km, and length in meters
- Reactance X = 0.08 Ω/km, the value IEC 60364-5-52 uses when no cable data is available
- Voltage drop (%) = voltage drop ÷ 400 V (three-phase, line to line) or 230 V (single-phase) × 100
- Voltage drop per amp per metre (mV/A/m) = b × (R × power factor + X × sin φ), the unit of the voltage drop tables in BS 7671 — multiply it by the current and the length in meters and divide by 1,000 to get volts
- Smallest size within the limit = the first standard size from 1.5 to 630 mm² whose drop is at or below the allowed percentage
Voltage drop table for copper cables (mV/A/m)
Voltage drop per amp per metre for each copper size from 1.5 to 630 mm², with the conductor at 90 °C (XLPE) and X = 0.08 Ω/km, from the formula above. Multiply by the design current (A) and the one-way route length (m), then divide by 1,000 for the drop in volts. A cable maker’s data for the actual cable and installation method takes precedence.
| Copper size (mm²) | Three-phase, pf 1 | Three-phase, pf 0.85 | Single-phase, pf 0.85 |
|---|---|---|---|
| 1.5 | 26.7 | 22.8 | 26.3 |
| 2.5 | 16.4 | 14 | 16.1 |
| 4 | 10.2 | 8.73 | 10.1 |
| 6 | 6.8 | 5.85 | 6.76 |
| 10 | 4.04 | 3.51 | 4.05 |
| 16 | 2.54 | 2.23 | 2.58 |
| 25 | 1.61 | 1.44 | 1.66 |
| 35 | 1.16 | 1.06 | 1.22 |
| 50 | 0.855 | 0.799 | 0.923 |
| 70 | 0.592 | 0.576 | 0.665 |
| 95 | 0.426 | 0.435 | 0.503 |
| 120 | 0.338 | 0.36 | 0.416 |
| 150 | 0.274 | 0.306 | 0.353 |
| 185 | 0.219 | 0.259 | 0.299 |
| 240 | 0.167 | 0.215 | 0.248 |
| 300 | 0.133 | 0.186 | 0.215 |
| 400 | 0.104 | 0.161 | 0.186 |
| 500 | 0.0808 | 0.142 | 0.164 |
| 630 | 0.0625 | 0.126 | 0.146 |
Example, with the calculator’s starting values: 100 A over a one-way route of 80 m on 35 mm² XLPE cable, three-phase, power factor 0.85 — 1.06 mV/A/m × 100 A × 80 m ÷ 1,000 = 8.5 V, or 2.1% of 400 V, within a 3% limit.
Which limit to use
IEC 60364-5-52 (Annex G) gives guide values for the drop from the origin of an installation to the equipment: 3% for lighting and 5% for other uses where the installation is supplied from a public low-voltage network, and 6% and 8% where it has its own transformer. BS 7671 (Appendix 4) uses the same values. Designers usually split the allowance between the feeder and the final circuits. Use the limit that your designer, the utility or the applicable code sets — in Thailand, the EIT electrical installation standard.
Voltage drop is one check of several
- Current-carrying capacity for the installation method, grouping and ambient temperature
- Short-circuit withstand of the conductor, coordinated with its protective device
- Earth fault loop impedance, so that the protective device disconnects in time
- Motor starting — the momentary drop when a large motor starts direct on line is several times the running drop
Next, see our power and control cables or size the transformer, then send your cable schedule for a quotation.
Keep reading
Related.
Bangkok Cable, Hanhe and ZTT
Power and control cables.
Low-, medium- and high-voltage cables, fire-resistant and control cables, and overhead conductors from Bangkok Cable, Hanhe and ZTT — supplied by the drum for projects in Thailand, and exported to the UAE, Saudi Arabia and the Maldives.
See the products: Power and control cables.Calculator
Transformer kVA calculator.
Estimate the transformer rating for a building or site from its load — a quick check before you request a quotation.
Open the calculator: Transformer kVA calculator.